A reading of 0 Ω (shorted) or Infinity / OL (open line) means the sensor has failed and needs replacement — neither is a valid point on this curve.
Full Reference Table click any row to load it above
°F
°C
Ohms
Data verified against BAPI's official 10K-2 (Type II NTC) output table — R25°C = 10,000 Ω ±3%, B25/85°C = 3975 K ±1.5%. Table steps in even 2°F increments from −39°F to 187°F with no gaps. Values interpolate linearly between the two nearest table points; resistance interpolates on a log scale vs. temperature, consistent with NTC thermistor physics.